general information:
Transmitter CVT 500 convert current or voltage signals to proportional industry standard signals. Direct measurement of currents up to 5 A and voltages up to 400 V are possible. For larger alternating currents a current converter and for larger alternating voltages a voltage converter is needed.
- measuring input for DC- and sinusoidal AC-signals
- arithmetic average value measurement RMS calibrated
- frequency range 40 Hz to 200 Hz
specifications:
auxiliary energy | |
auxiliary voltage: |
230 V AC ±10 % or 24 V DC ±15 % |
frequency AC: | 47 Hz to 63 Hz |
power consumption: | <3 VA |
operating temperature: | -10°C to +50°C |
CE conformity: | EN 61326-1:2013; EN 60664-1:2007 |
|
|
inputs | |
accuracy: | ≤ 0.5 % (≤ 0.2 % single adjustment) |
frequency AC: | 40 Hz to 200 Hz (other ranges upon request) |
standard measuring ranges | |
current: | 0 A to 1 A and 0 A to 5 A (sinusoidal) or DC |
Ri: | 20 mΩ (5 A-input) or 100 mΩ (1 A-input) |
over-load: | 2-times, 4-times for max. 5 s |
voltage: | 0 V to 125 V and 0 V to 250 V AC or DC |
Ri: |
600 kΩ (125 V-input) or 1.2 MΩ (250 V-input) |
over-load: |
max. 500 V AC/DC |
custom measuring ranges |
|
voltage: | end value in range 0.1 to 400 V AC/DC |
Ri: |
4.8 kΩ/V |
over-load: |
5-times UN, max. 500 V AC/DC |
current: |
end value in range 0.001 to 5 A AC/DC |
Ri: |
100 mΩ ÷ (measuring range [A]) |
over-load: |
2-times, 4-times for max. 5 s |
end value: |
adjustable ±5 % |
|
|
output |
|
output changing |
|
voltage/current: |
link between terminal 8 and 9 |
current output: |
0/4 mA to 20 mA selectable, burden ≤500 Ω |
rise time (T90): |
<650 ms |
burden error: |
<0.1 % (RL = <200 Ω), <0.2 % (RL = <500 Ω) |
voltage: |
0/2 V to 10 V selectable, load max. 10 mA |
|
|
housing |
|
type: |
polycarbonate, UL 94 V-0 TS35 acc. to DIN EN 60715:2001-09 |
weight: |
approx. 200 g |
connection: |
screw terminals, max. 2.5 mm2 |
ingress protection: |
housing IP30, terminals IP20 acc. to BGV A3 |
For further details p.r.t. data sheet:
instruction manual as .pdf: