Deutsch  English 


isolating signal converter (model with characteristic curve increasing) | TV500L

isolating signal converter (model with characteristic curve increasing) | TV500L


152,00 EUR

 inkl. 19 % USt  -> Preis zzgl. Versandkosten

Lieferzeit bzw. Fertigungszeit variiert - bitte erfragen!

Art.Nr.: TV500L (steigend)
construction type:
100: input 0/4…20 mA, 0/2…10 V DC, output 0/4...20 mA, 0/2...10 V DC:
110: input 0/4…20 mA, 0/2…10 V DC, output ± 20 mA /± 10 V DC (+ 51,00 EUR) :
200: input ± 20 mA /± 10 V DC, output 0/4…20 mA, 0/2…10 V DC (+ 51,00 EUR) :
210: input ± 20 mA /± 10 V DC, output ± 20 mA /± 10 V DC (+ 51,00 EUR) :
characteristic curve:
0: increasing:
auxiliary voltage:
0: 230 V AC | ±10 %:
5: 24 V DC | ±15 %:

Bitte beachten Sie stets die Bestellhinweise auf den einzelnen Datenblättern!

Produktbeschreibung


general information:

Isolating signal converters of the series TV500L can be used to isolate and convert unipolar or bipolar standard signals. The output characteristic curve can be selected for increasing or decreasing performance. The small housing width allows a space-saving installation.


specifications:

auxiliary energy

auxiliary voltage: 230 V AC ±10 % or 24 V DC ±15 %
frequency AC: 47 Hz to 63 Hz
power consumption: <3 VA (at 24 V DC 80 mA)
working temperature:-10°C to +50°C
CE conformity:EN 55022, EN 60555,
IEC 61000-4-3/4/5/11/13
EMV:EN 61326-1:2013; EN 60664-1:2007


inputs
current:±20 mA or 0/4 mA to 20 mA switchable,
Ri = 43 Ω, overload max. 100 mA
voltage:±10 V or 0/2 V to 10 V switchable,
Ri = 40 kΩ, overload max. 100 V
start value:adjustable ±1.5 %
end value:adjustable ±1.5 %
accuracy:<0.3 %, (single range adjustment <0.1 %)


output
programmable output
voltage / current:
link between terminal 8 and 9
current:0/4 mA to 20 mA switchable, burden ≤400 Ω;
±20 mA, burden ≤150 Ω
burden error:<0.1 % (RL = 0 Ω to 200 Ω),
<0.2 % (
RL = 0 Ω to 400 Ω)
voltage:0/2 V to 10 V switchable, load max. 10 mA;
±10 V, load max. 5 mA
rise time (T90):<40 ms


housing
model:standard case made of Makrolon 8020 UL94V-1 acc. to DIN EN 60715:2001-09, TS35
weight:approx. 200 g
connection:screw terminals, max. 2.5 mm2
ingress protection:case IP30,
terminals IP20, acc. to BGV A3

 




For further details p.r.t. data sheet:





instruction manual as .pdf:

 

 

 

Empfohlenes Zubehör | Weitere Artikel

Trennverstärker (Ausführung mit Kennlinie fallend) | TV500L

Trennverstärker (Ausführung mit Kennlinie fallend) | TV500L

203,00 EUR

Warenkorb

Sie haben noch keine Artikel in Ihrem Warenkorb.

Warenkorb »

Herzlich willkommen

E-Mail-Adresse:
Passwort:
Passwort vergessen?

Top Artikel