universal isolating amplifier | TV125L
117,50 EUR
inkl. 19 % USt -> Preis zzgl. Versandkosten
Lieferzeit bzw. Fertigungszeit variiert - bitte erfragen!
Art.Nr.: TV125LProduktbeschreibung
general information:
- safe galvanic isolation between input / output / auxiliary voltage with reinforced isolation in accordance with DIN EN 61010-1
- step response T90 40 ms
- output deviation <0.2% of the limit value
- overload protection of the current input with automatically resetting fuse
- operating display and status messages via two-colour LED
- configuration via front DIP switches
- plug-in terminal strips
- narrow installation width of 12.5 mm for carrier rail mounting TS 35
specifications:
auxiliary power | |
auxiliary voltage: | 18 to 30 V DC |
power consumption: |
<0.5 VA |
conformity: | CE, directive 2004/108/EG |
EMV: | DIN EN 61326-1: 2013-07 |
standards: | DIN EN 61010-1: 2011-07, DIN EN 61010-2-30: 2011-07 |
rated voltage: | 300 V AC/DC acc. to DIN EN 61010-1 with overvoltage category 2 and degree of contamination 2 between all circuits. Safe separation with amplified isolation. |
test voltage: | 3 kV AC, 50 Hz, 1 min input / output / auxiliary power |
environmental conditions | |
working temperature: | -10°C to +60°C |
storage temperature: | -20°C to +60°C |
air humidity: | <95 % (no condensation) |
inputs | |
voltage input: | switchable 0 V to 10 V or 2 V to 10 V. Ri = 47 kΩ. Max. overload 32 V AC/DC |
current input: | switchable 0 mA to 20 mA or 4 mA to 20 mA. Ri = 48 Ω + 15 Ω (RiPTC). Max. overload 32 V AC/DC acc. to DIN EN 61010-2-30 |
output | |
current output: | switchable 0 mA to 20 mA or 4 mA to 20 mA. Load <150 Ω. |
step response: | 40 ms |
standard error: | <0.2 % of final value |
temperature coefficient: | <0.01 % / K |
housing | |
material: | Polyamide (PA) 6.6, UL94V-0 |
weight: | 91 g |
ingress protection: | housing IP30, terminals IP20 BGV A3 |
colour: | light grey |
installation width: | 12.5 mm |
dimensions (HxT): | 108 x 114 mm |
installation: | carrier rail mounting TS35 DIN EN 60715 |